PCE-PA 8300 Power Analyzer

$0.00

PCE-PA 8300 Three Phase Power Data Logger 3-phase / 3 current clamps / LCD graphic display / SD card memory
Category:

Description

PCE-PA 8300 Three Phase Power Data Logger
3-phase / 3 current clamps / LCD graphic display / SD card memory

The PCE-PA 8300 is a Three Phase Power Data Logger that features a durable enclosure, SD card memory, a LCD graphic display, as well as apparent, effective, and reactive power measurement. The easy-to-use PCE-PA 8300 Three Phase Power Data Logger is the ideal tool for performing power and harmonics analysis as well as for measuring network capacity.

The PCE-PA 8300 is available for purchase in two different configurations:

Set 1: Includes 3 current clamps for measurements up to 1200 A AC
Set 2: Includes 3 flexible Rogowski coils for measurements up to 3000 A AC (for an additional fee)

Please choose either Set 1 or Set 2 before adding the PCE-PA 8300 to your cart.

Highlights

– Voltage measurement range of 10 V … 600 V AC
– Current measurement range of 20 A … 1200 A AC (Set 1) or 30 A … 3000 A AC (Set 2)
– Performance measurement range of 0 kW … 9.999 MW (VA/VAR)
– SD card memory
– LCD graphic display
– Durable enclosure
– Compatibility with various manufacturers’ power clamps
– Adjustable back-up interval, allowing for long-term data collection
– Auto-setting of measurement range (AC V)
– Power efficiency, delay angle, and frequency measurement
– Apparent, effective, and reactive power measurement
– Harmonic spectrum measurement up to the 50th order

Specifications

Electrical specifications
Voltage Measurement (AC V)
Measurement Range Resolution Accuracy
10 V … 600 V (phase to neutral) 0.1 V ±(0.5 % + 0.5 V)
10 V … 600 V (phase to phase 0.1 V ±(0.5 % + 0.5 V)
Current Measurement (AC A) Set 1
Measurement Range Resolution Accuracy
20 A 0.001 A (< 10 A)
0.01 A (≥ 10 A)
± (0.5 % + 0.1 A)
200 A 0.01 A (< 100 A)
0.1 A (≥ 100 A)
± (0.5 % + 0.5 A)
1200 A 0.1 A (< 1000 A)
1 A (≥ 1000 A)
± (0.5 A + 5 A)
Current measurement (AC A) Set 2
Measurement range Resolution Accuracy
30 A 0.001 A (< 10 A)
0.01 A (≥ 10 A)
±(0.5 % + 0.1 A)
300 A 0.01 A (< 10 A)
0.1 A (≥ 10 A)
±(0.5 % + 0.5 A)
3000 A 0.1 A (< 1000 A)
1 A (≥ 1000 A)
±(0.5 A + 5 A)
Effective power
Measurement range Resolution Accuracy
0 KW … 9.999 KW 0.001 KW ±(1 % + 0.008 KW)
10 KW … 99.99 KW 0.01 KW ±(1 % + 0.08 KW)
100 KW … 999.9 KW 0.1 KW ±(1 % + 0.8 KW)
1 MW … 9.999 MW 0.001 MW ±(1 % + 0.008 MW)
Apparent Power
Measurement range Resolution Accuracy
0 KVA … 9.999 KVA 0.001 KVA ±(1 % + 0.008 KVA)
10 KVA … 99.99 KVA 0.01 KVA ±(1 % + 0.08 KVA)
100 KVA … 999.9 KVA 0.1 KVA ±(1 % + 0.8 KVA)
1 MVA … 9.999 MVA 0.001 MVA ±(1 % + 0.008 MVA)
Reactive Power
Measurement range Resolution Accuracy
0 KVAR … 9.999 KVAR 0.001 KVAR ±(1 % + 0.008 KVAR)
10 KVAR … 99.99 KVAR 0.01 KVAR ±(1 % + 0.08 KVAR)
100 KVAR … 999.9 KVAR 0.1 KVAR ±(1 % + 0.8 KVAR)
1 MVAR … 9.999 MVAR 0.001 MVAR ±(1 % + 0.008 MVAR)
Active Energy
Measurement range Resolution Accuracy
0 KWH … 9.999 KWH 0.001 KWh ±(2 % + 0.008 KWh)
10.00 KWH … 99.99 KWH 0.01 KWh ±(2 % + 0.08 KWh)
100.0 KWH … 999.9 KWH 0.01 KWh ±(2 % + 0.8 KWh)
1 MWH … 9.999 MWH 0.001 MMh ±(2 % + 0.008 MWh)
Apparent Energy
Measurement range Resolution Accuracy
0 KVARH … 9.999 KVARH 0.001 KVARh ± (2 % + 0.008 KVARh)
10.00 KVARH … 99.99 KVARH 0.01 KVARh ± (2 % + 0.08 KVARh)
100.0 KVARH … 999.9 KVARH 0.01 KVARh ± (2 % + 0.8 KVARh)
1 MVARH … 9.999 MVARH 0.001 MVARh ± (2 % + 0.008 MVARh)
Power Factor
Measurement range Resolution Accuracy
0 … 1 0.01 ± 0.04
Delay Angle
Measurement range Resolution Accuracy
-180° … +180° 0.1° ±1°
Frequency
Measurement range Resolution Accuracy
45 Hz … 65 Hz 0.1 Hz ± 0.1 Hz
Harmonic of AC Voltage at 50 / 60 Hz
Measurement range Resolution Accuracy
1 … 20th order 0.001 … 1 A
0.1 %
± (2 % + 0.5 A)
± (2 % + 10 Digit)
21 … 30th order 0.001 … 1 A
0.1 %
± (2 % + 0.5 A)
± (2 % + 10 Digit)
21 … 50th order 0.001 … 1 A
0.1 %
not specified
General specifications
Display 3.7 in / 94.0 mm point-matrix LCD (320 * 240 pixel) with LED background lights
Safety standards IEC1010CAT III 600V
Input resistance AC V 10 MOhm
Operating frequency of current clamp 40 Hz … 1 kHz
Tested operating frequency of current clamp 45 Hz … 65 Hz
Overload protection AC V
AC A
720 V RMS
1300 A with current clamp
Data Storage SD memory card
Recording interval 1 second
Data logging function logging with real-time speed on SD memory card
Filing interval 2 … 7200 seconds
Data output (only for live display on computer) per USB or RS232, depending on connection cable
Operating temperature 0° C … +50° C / 32° F … 122° F
Surrounding humidity < 80 % RH
8 x 1.5 V AA batteries
Voltage Supply 9 V adapter
Current Drain Measurement Device: 300 mA DC
current clamp: 34 mA DC
Maximum Wire Diameter 50 mm / 1.9 in
Weight Measurement Device: 948 g / 33.4 oz (incl. battery)
Current clamp: 467 g / 16.4 oz (incl. cable)
Dimensions Device: 225 mm x 125 mm x 64 mm / 8.8 in x 4.9 in x 2.5 in
Current clamp: 210 mm x 64 mm x 33 mm / 8.2 in x 2.5 in x 1.2 in
Clamp jaw: 86 mm / 3.3 in (exterior)

Delivery Scope

1 x PCE-PA 8300 Three Phase Power Data Logger
3 x Current clamps (Set 1) or 3 x flexible Rogowski coils (Set 2)
4 x Insulated alligator clips
4 x Safety test lines
6 x 1.5 V AA batteries
1 x 9 V mains adapter
1 x SD memory card
1 x Carrying case
1 x User manual

Downloads

Download Datasheet

Download User Manual

TOP